Re-map Desk Instructions - Trafficware
When an iCCU-S/S2 system is operating in SDLD/BIU mode, the traffic controller must be remapped for it to see pedestrian calls over BIU. Use the following procedure for Trafficware or similar traffic controllers:
Configure Detector Rack BIU for Pedestrian Calls (example is BIU#2)
Add Detector Rack Device (Need to add the second detector rack to enable the SDLC signaling to it)
- Main Menu (older Trafficware firmware)
- Select β1βController
- Select β3β Chan, SDLC
- Select β7β SDLC Devcs
- Main Menu (Newer Trafficware firmware)
- Select β1βController
- Select β3β Chan, SDLC
- Select β1β TS2 Devcs
- Move cursor to the right, under Detector 2
- Select β1β to enable
- Press βENTRβ key to save
- Main Menu (older Trafficware firmware)
Detector Rack Re-mapping
- For Detector BIU 2: Map the input functions Veh Call 17, Veh Call 18, Veh Call 19, and Veh Call 20 to Ped Call 2, Ped Call 4, Ped Call 6 and Ped Call 8, respectively
- For Detector BIU 3: Map Veh Call 33, Veh Call 34, Veh Call 35, and Veh Call 36 to Ped Call 2, Ped Call 4, Ped Call 6 and Ped Call 8, respectively
- For Detector BIU 4: Map Veh Call 49, Veh Call 50, Veh Call 51, and Veh Call 52 to Ped Call 2, Ped Call 4, Ped Call 6 and Ped Call 8, respectively
- On the Trafficware controller Vehicle Call inputs 1-64 are input function numbers 1-64, respectively
- The Ped Call inputs 1-8 are input function numbers 129-136, respectively
- For a standard 4 ped phase intersection only input functions 130 (phase 2), 132(phase 4), 134 (phase 6), 136 (phase 8) are used
- Go to the βIO Logicβ menu to re map the functions.
- Main Menu (older Trafficware firmware)
- Select β1β Controller
- Select β3β Chan, SDLC
- Select β9β IO Mapping
- Select β1β IO Logic
- Main Menu (newer Trafficware firmware)
- Select β1β Controller
- Select β8β Channel IO
- Select β7β IO Logic
- Set according to table (enter the vehicle call function number on the right and the ped call function on the left) (Detector 2 re-mapping shown)
- Main Menu (older Trafficware firmware)
Result | FCN | |
I130 | = |
I17 |
I132 | = |
I18 |
I134 | = |
I19 |
I130 | = |
I20 |
- Press βENTRβ key to save.
Configure Terminals and Facilities BIU 2 with Flash Status
Re-Map Flash to Output Logic 1 function
- Main Menu
- Select β1β Controller
- Select β3β Chan, SDLC
- Select β9β IO Mapping
- Select β1β IO Logic
- Move the cursor down to find an open row (the first 4 rows were used to re-map veh calls to ped calls previously)
- Set according to table:
Result | Fcn (function) | Oper (Operator) | Fcn (function) | |
O230 | = | I208 | OR | I206 |
- Press βENTRβ key to save
Map Flash Logic to Terminal and Facilities BIU 2 Ouput
- Main Menu
- Select β1β Controller
- Select β3β Chan, SDLC
- Select β9β IO Mapping
- Select β2β IO Map
- Move cursor to the right twice to edit BIU 2
- Move cursor down to row 36
- Set the output code to 230
- Press βENTRβ key to save.
Trafficware Remap Desk Instructions PDF
Revision 0.1