Re-map Desk Instructions - Naztec

When an iCCU-S/S2 system is operating in SDLD/BIU mode, the traffic controller must be remapped for it to see pedestrian calls over BIU. Use the following procedure for Naztec Series 900 or similar traffic controllers:

  • Configure Detector Rack BIU for Pedestrian Calls (example is BIU#2)

    • Add Detector Rack Device (Need to add the second detector rack to enable the SDLC signaling to it)

      • Main Menu
      • Select β€œ1”Controller
      • Select β€œ3” Chan, SDLC
      • Select β€œ7” SDLC Devcs
      • Move cursor to the right, under Detector 2
      • Select β€œ1” to enable
      • Press β€œENTR” key to save

    • Detector Rack Re-mapping

      • Map the input functions Veh Call 17, Veh Call 18, Veh Call 19, and Veh Call 20 to Ped Call 2, Ped Call 4, Ped Call 6 and Ped Call 8, respectively.
      • Input function numbers: Veh Call 17 = 17, Veh Call 18 = 18, Veh Call 19 = 19, Veh Call 20 = 20, Ped Call 2 = 130, Ped Call 4 = 132, Ped Call 6 = 134, Ped Call 8 = 136.
      • Main Menu
      • Select β€œ1” Controller
      • Select β€œ3” Chan, SDLC
      • Select β€œ9” IO Mapping
      • Select β€œ1” IO Logic
      • Set according to table (enter the vehicle call function number on the right and the ped call function on the left) (Detector 2 re-mapping shown)
Result
FCN
I130

=

I17
I132

=

I18
I134

=

I19
I130

=

I20

      • Press β€œENTR” key to save.

        Configure Terminals and Facilities BIU 2 with Flash Status

    • Re-Map Flash to Output Logic 1 function

      • Main Menu
      • Select β€œ1” Controller
      • Select β€œ3” Chan, SDLC
      • Select β€œ9” IO Mapping
      • Select β€œ1” IO Logic
      • Move the cursor down to find an open row (the first 4 rows were used to re-map veh calls to ped calls previously)
      • Set according to table:
Result
Fcn (function) Oper (Operator) Fcn (function)
O230 = I208 OR I206

      • Press β€œENTR” key to save
    • Map Flash Logic to Terminal and Facilities BIU 2 Ouput

      • Main Menu
      • Select β€œ1” Controller
      • Select β€œ3” Chan, SDLC
      • Select β€œ9” IO Mapping
      • Select β€œ2” IO Map
      • Move cursor to the right twice to edit BIU 2
      • Move cursor down to row 36
      • Set the output code to 230

      • Press β€œENTR” key to save.

Naztec Remap Desk Instructions PDF

Revision 0.1