Re-map Desk Instructions - Intelight
When an iCCU-S/S2 system is operating in SDLD/BIU mode, the traffic controller must be remapped for it to see pedestrian calls over BIU. Use the following procedure for Intelight traffic controllers:
Initialize
This instruction uses the front panel display, but the web server can be used for easier configuration.
Connect computer to internal Web server for easier configuration.
User Ethernet adapter 2 with IP address 10.20.70.51.
Set connect computer IP address to 10.20.70.100, Subnet mask:255.255.255.0.
Web server is at 10.20.70.51.
Configure Detector Rack BIU for Pedestrian Calls
- Add Detector Rack Device (need to add the second detector rack to enable the SDLC signaling to it)
- Front Panel Manager – Select “1 MaxTime”
- Main Menu – Intelight MaxTime x.x.x
- Select “2. Controller”
- Select “9. More”
- Select “2. Advanced IO”
- Select “1. IO Modules”
- Add “TS2 DR2 BIU” to Module 6
- Detector Rack Re-mapping
- Need to map detector to ped detectors.
- Front Panel Manager – Select “1 MaxTime”
- Main Menu – Intelight MaxTime x.x.x
- Select “2. Controller”
- Select “9. More”
- Select “2. Advanced IO”
- Select “3. Input Points”
- Enter the IO Module number “6” and press “ENT”.
- Use the arrow keys to move the cursor to the Control type of the first row.
- Use the “-“ button to change the “Control Type” from “Veh Det Call” to “Ped Det Call”.
- Use the “→” button to move to the curser to the “Index” column and press “2”.
- Repeat for the next 7 rows, so the mapping looks as follows:
Input | Desc | Control Type | Index |
1 | I/0 1 | Ped Det Call | 2 |
2 | I/0 2 | Ped Det Call | 4 |
3 | I/0 3 | Ped Det Call | 6 |
4 | I/0 4 | Ped Det Call | 8 |
5 | I/0 5 | Ped Det Call | 1 |
6 | I/0 6 | Ped Det Call | 3 |
7 | I/0 7 | Ped Det Call | 5 |
8 | I/0 8 | Ped Det Call | 7 |
Configure Terminals and Facilities BIU 2 for Flash
- Create User Program Definition
- Front Panel Manager – Select “1 MaxTime”
- Main Menu – Intelight MaxTime x.x.x
- Select “2. Controller”
- Select “9. More”
- Select “7. User Programs”
- Select “2. Definition”
- Type a Program number “1” and hit enter. (You can use any program number if “1” is used.)
- In the top row use the right arrow key to move the cursor the “Result” column.
- Use the plus key to Select “Unit Alarm”.
- Use the right arrow key to move the cursor to the “Ind” column.
- Type “2” for the index.
- Use the right arrow key to move the cursor to the “Operation” column.
- Use the plus key to Select “R=(A OR B)”.
- Use the right arrow key to move the cursor to the “Param A” column.
- Use the plus key to Select “MMU Flash”.
- Use the right arrow key to move the cursor to the “Param B” column.
- Use the plus key to Select “Local Flash”.
- Exit this screen.
- Map Defined Alarm to Terminal and Facilities BIU 2 Ouput
- Assign the defined unit alarm from the previous step to one of four spare I/O Pins on TF BIU 2. The IO Pin number will have to match the configuration in the iCCU.
- Front Panel Manager – Select “1 MaxTime”
- Main Menu – Intelight MaxTime x.x.x
- Select “2. Controller”
- Select “9. More”
- Select “2. Advanced IO”
- Select “4. Output Points”
- When prompted for “IO Module”, type “4” and press the “ENT” key.
- In the “Desc” column use the down arrow key to move the cursor to the row with “Desc” “I/O 21”, “I/O 22”, “I/O 23”, or “I/O 24”.
- Use the right arrow key to move the cursor to the “Control Type” column.
- Use the plus key to select “Alarm Status”.
- Use the right arrow key to move the cursor to the “Index” column.
- Type a “2” for the index which should match the index in section 3.1.
- Exit this menu.
- Create User Program Definition
Intelight Remap Desk Instructions PDF
Revision 0.1